Analysis of the Effect of Harmonic Distortion on the Performance of a 1600 Kva Distribution Transformer in an Industrial Electrical System Using Matlab/Simulink

Authors

  • Novita Vadina Marta Ria Power Plant Engineering Technology, Faculty of Vocational Studies, State University Of Malang, Malang, Indonesia
  • Royb Fatkhur Rizal Power Plant Engineering Technology, Faculty of Vocational Studies, State University Of Malang, Malang, Indonesia
  • Muhammad Afnan Habibi Faculty of Engineering, University of Leeds, Leeds, LS2 9JT, UK

DOI:

https://doi.org/10.35718/ismatech.v4i2.8482342

Keywords:

Harmonic distortion, 1600 kVA transformer, THD-I, Matlab/SIMULINK, Power Quality

Abstract

Distribution transformers are important components in industrial electrical systems because their performance is affected by power quality conditions, particularly harmonic distortion generated by nonlinear loads. This study aims to analyze the effect of harmonic distortion on the performance of a 1600 kVA distribution transformer and to compare field measurement results with simulation results using MATLAB and Simulink. Real measurements were conducted by using a Hioki PQ3198 and PQ One program on the distribution panel of the transformer. Measurement results showed THD-I values of 6.53% for phase R, 7.58% for phase S, and 7.50% for phase T, with an average apparent power of 307.1 kVA. MATLAB analysis was carried out with the variation of THD-I in the range of 0% to 20% to assess the effect on the RMS current, loading, and the copper loss index. However, Simulink analysis was performed using the nonlinear load, specifically a six-pulse diode rectifier. RMS current calculations based on fundamental current and THD yielded 462.282 A, 439.658 A, and 454.373 A for phases R, S, and T, respectively; meanwhile, the rectifier model produced a THD-I of 12.7159%, with the 5th harmonic (H5) component at 51.6665 and the 7th harmonic (H7) at 19.5684. These findings show that an increase in THD-I increases the effective current from a mathematical perspective, while a six-pulse rectifier gives rise to more distortion compared to the average case studied in practice.

Author Biographies

Novita Vadina Marta Ria, Power Plant Engineering Technology, Faculty of Vocational Studies, State University Of Malang, Malang, Indonesia

Undergraduate Student

Royb Fatkhur Rizal, Power Plant Engineering Technology, Faculty of Vocational Studies, State University Of Malang, Malang, Indonesia

Senior Lecturer

Muhammad Afnan Habibi, Faculty of Engineering, University of Leeds, Leeds, LS2 9JT, UK

Lecturer

References

[1] B. W. Dionova, T. Hidayat, S. Wilyanti, M. N. Mohammed, and D. J. Vresdian, “Jurnal Nasional Teknik Elektro Distribution Transformer Synchronization Simulation and Implementation with Dyn5 and Dyn11 Vector Groups using the MATLAB Simulink and TTR Test,” vol. 3, 2022.

[2] Yudhistira et al., “Karakterisasi Conducted Emission Noise pada Inverter di Sistem Photovoltaic Off-Grid,” J. Nas. Tek. Elektro dan Teknol. Inf., vol. 10, no. 1, pp. 100–109, 2021, doi: 10.22146/jnteti.v10i1.1066.

[3] D. Teknik and U. G. Mada, “Analisis Harmonik dan Perbaikan Nilai THD Arus dengan Perancangan Filter Pasif Single-Tuned,” vol. 12, no. 4, pp. 892–906, 2024.

[4] R. Amalia, “ISSN : 2302 - 2949 PEMODELAN DAN SIMULASI BEBAN NON-LINIER 3-FASA,” no. 2, pp. 165–171, 2015.

[5] A. Zulkarnaini, R. Sinambela, and L. Lisapaly, “LISTRIK DI GEDUNG ADMINISTRASI UNIVERSITAS JAYABAYA,” no. 3, pp. 132–139, 2024, doi: 10.14710/transmisi.26.3.132-138.

[6] X. Ma, R. Jia, C. Liang, H. Du, X. Dong, and M. Ding, “Study of Transformer Harmonic Loss Characteristic in Distribution Network Based on Field-Circuit Coupling Method,” 2022.

[7] T. According, C. Standard, C. Andrada-monr, and Á. Juan, “Load Losses and Short-Circuit Resistances of Distribution Transformers According to IEEE Standard C57.110,” no. 1, 2023.

[8] D. Naval Architecture et al., “Design of the electrical system on a general cargo ship with a length of 105,669 meters,” Indones. J. Marit. Technol., vol. 1, no. 2, pp. 60–64, 2023, doi: 10.35718/ismatech.v1i2.1044.

[9] Yohan Fajar Sidik, F. Danang Wijaya, Roni Irnawan, Muhammad Ridwan, Kevin Gausultan, and Sriyono, “Single-Phase Shift Modulation of DAB Converter in Typhoon HIL Simulation,” J. Nas. Tek. Elektro dan Teknol. Inf., vol. 13, no. 1, pp. 1–10, 2024, doi: 10.22146/jnteti.v13i1.6876.

[10] S. Suardi et al., “Determination of Electrical Power for Lighting Distribution Using LED Lights on KM. Tuna Kita,” Indones. J. Marit. Technol., vol. 3, no. 1, pp. 1–10, 2025, doi: 10.35718/ismatech.v3i1.1287.

[11] S. Saodah, I. M. Wiwit, A. Deni, and D. Sodiq, “Pengaruh Harmonisa Penggerak Kecepatan Variabel terhadap Kinerja Motor DC Fan Test Set,” vol. 9, no. 3, pp. 505–517, 2021.

[12] A. Syarifuddin et al., “Jurnal Nasional Teknik Elektro Minimizing THD Using a Multilevel Inverter Integrated with MPPT,” vol. 2, 2025.

[13] A. Abdali, K. Mazlumi, and A. Rabiee, “International Journal of Electrical Power and Energy Systems Harmonics impact on hotspot temperature increment of distribution transformers : Nonuniform magnetic-thermal approach,” Int. J. Electr. Power Energy Syst., vol. 157, no. December 2023, p. 109826, 2024, doi: 10.1016/j.ijepes.2024.109826.

[14] D. Committee, I. Power, and E. Society, “IEEE Std 519-2014,” "IEEE Recomm. Pract. Requir. Harmon. Control Electr. Power Syst. IEEE Std 519-2014 (Revision IEEE Std 519-1992), vol. 2014, pp. 1–29, 2014, [Online]. Available: https://ieeexplore.ieee.org/servlet/opac?punumber=6826457

[15] P. Systems and E. Committee, IEEE Recommended Practice for Electric Power Distribution for Industrial Plants, vol. 1993. 1993.

[16] J. Yaghoobi, A. Alduraibi, D. Martin, F. Zare, and D. Eghbal, “Electrical Power and Energy Systems Impact of high-frequency harmonics ( 0 – 9 kHz ) generated by grid-connected inverters on distribution transformers ☆,” Electr. Power Energy Syst., vol. 122, no. October 2019, p. 106177, 2020, doi: 10.1016/j.ijepes.2020.106177.

[17] M. I. Iskandar, Panca Mudjirahardjo, and Bambang Siswojo, “A Single Phase Inverter Using The Unipolar Sinusoidal Pulse Width Modulation Method,” J. EECCIS (Electrics, Electron. Commun. Control. Informatics, Syst., vol. 19, no. 1, pp. 29–38, 2025, doi: 10.21776/jeeccis.v19i1.1789.

[18] A. Rafiah and S. Hariyanto, “Energy Efficiency and Battery Load Sharing Analysis of 26-m Electric Supply Boat Using MATLAB,” vol. 04, no. 01, 2026.

[19] S. Suardi et al., “Optimizing Generator Power Usage Through LED Lighting Distribution on Tugboats: A Case Study of a 26.80-Meter Vessel,” Indones. J. Marit. Technol., vol. 3, no. 1, pp. 1–8, 2025, doi: 10.35718/ismatech.v3i1.1285.

[20] M. C. Bagaskoro, Aripriharta, Sujito, and S. Omar, “Optimizing PV Inverter GMPP and Current Harmonic Distortion Using QHBM,” J. Nas. Tek. Elektro, vol. 14, no. 3, pp. 162–172, 2025, doi: 10.25077/jnte.v14n3.1331.2025.

[21] V. Speed and P. T. Ikpp, “Analisis Pemasangan Filter Pasif Untuk Mereduksi Harmonisa,” vol. 8, no. 1, pp. 1–12, 2023, doi: 10.31849/sainetin.v8i1.10030.

[22] R. S. PAMUNGKAS and C. F. NUGRAHA, “Impact Analysis of Transformer Extension and Network Maneuvering Strategy on Tulungagung Substations,” ELKOMIKA J. Tek. Energi Elektr. Tek. Telekomun. Tek. Elektron., vol. 14, no. 1, p. 1, 2026, doi: 10.26760/elkomika.v14i1.1.

[23] A. SENEN, H. S. DINI, D. ANGGAINI, and P. PUTERA, “Penentuan Kriteria Kapasitas Transformator Berdasarkan Proyeksi Kebutuhan Energi secara Mikrospasial,” ELKOMIKA J. Tek. Energi Elektr. Tek. Telekomun. Tek. Elektron., vol. 10, no. 1, p. 200, 2022, doi: 10.26760/elkomika.v10i1.200.

[24] R. K. Antar and B. M. Saied, “Active power compensation circuit for resonance mitigation and harmonic reduction in microgrid system,” J. Mechatronics, Electr. Power, Veh. Technol., vol. 15, no. 1, pp. 32–41, 2024, doi: 10.55981/j.mev.2024.822.

[25] O. Penangsang, R. S. Wibowo, N. K. Aryani, M. D. Prasetyo, M. N. Arianto, and A. A. Lutfi, “Harmonic assessment on two photovoltaic inverter modes and mathematical models on low voltage network power quality,” Int. J. Electr. Comput. Eng., vol. 13, no. 6, pp. 5951–5965, 2023, doi: 10.11591/ijece.v13i6.pp5951-5965.

[26] Y. Siregar, F. Situmeang, and N. N. Mohamed, “Comparative design of harmonic current reduction in variable speed drive using space vector pulse width modulation and hybrid pulse width modulation,” Int. J. Electr. Comput. Eng., vol. 14, no. 5, pp. 4907–4920, 2024, doi: 10.11591/ijece.v14i5.pp4907-4920.

[27] D. O. Anggriawan, E. Wahjono, I. Sudiharto, and A. Budikarso, “Identification of Power Quality Disturbances Based on Fast Fourier Transform and Artificial Neural Network,” vol. 19, no. 1, pp. 9–17, 2023, doi: 10.17529/jre.v19i1.27120.

[28] S. A. Santoso and A. Ulinuha, “Harmonic Distortion Analysis Of On-grid Photovoltaic Panel Integration In Load Sharing Scheme,” Elkha, vol. 17, no. 1, pp. 77–83, 2025, doi: 10.26418/elkha.v17i1.91311.

[29] F. Rofii, D. Siswanto, G. Priyandoko, and S. Setiawati, “Rancang Bangun Alat Deteksi Gangguan Harmonisa Secara Real Time Berbasis Jaringan Syaraf Tiruan,” Transmisi, vol. 23, no. 3, pp. 119–124, 2021, doi: 10.14710/transmisi.23.3.119-124.

[30] A. A. Syahrin, D. O. Anggriawan, E. Prasetyono, E. Sunarno, and E. Wahjono, “Real-Time Detection of Power Quality Disturbance using Fast Fourier Transform and Adaptive Neuro-Fuzzy Inference System,” vol. 20, no. 1, pp. 12–19, 2024, doi: 10.17529/jre.v20i1.33695.

[31] H. Prasetijo, P. Priswanto, W. H.P., and I. Irunowo, “Analisa Pemasangan Filter Pasif Sebagai Peredam Harmonisa Akibat Beban Non Linier,” JRST (Jurnal Ris. Sains dan Teknol., vol. 7, no. 1, p. 109, 2023, doi: 10.30595/jrst.v7i1.16677.

[32] A. Irawan, Zulfahri, and Monice, “orde harmonik,” SainETIn J. Sains, Energi, Teknol. dan Ind., vol. 9, no. 1, pp. 24–31, 2024, doi: 10.31849/sainetin.v9i1.10913.

[33] A. R. Lubis, A. Sutopo, and M. Affandi, “Analisis Harmonisa Pada Trainer Lab Generator Sinkron Tiga Fasa NV7017,” JTEIN J. Tek. Elektro Indones., vol. 4, no. 2, pp. 566–572, 2023, doi: 10.24036/jtein.v4i2.452.

[34] H. Setiawan, B. Y. Dewantara, and I. Winarno, “Eliminasi Harmonisa Pada Induction Furnace Menggunakan Filter Hybrid,” E-Link J. Tek. Elektro dan Inform., vol. 19, no. 1, p. 116, 2024, doi: 10.30587/e-link.v19i1.7219.

Downloads

Published

2026-10-07

How to Cite

Ria, N. V. M., Rizal, R. F., & Habibi, M. A. (2026). Analysis of the Effect of Harmonic Distortion on the Performance of a 1600 Kva Distribution Transformer in an Industrial Electrical System Using Matlab/Simulink. Indonesian Journal of Maritime Technology, 4(2). https://doi.org/10.35718/ismatech.v4i2.8482342